About TL-5™
TL-5™ is both versatile and economical, making it perfect for wall panelling, cladding or even short span roofing. The TL-5™ profile is quick and easy to install, long lasting and durable. With a rib height of 28mm, a large sheet coverage of 762mm, and specially design capillary grooves, TL-5™ offers excellent value for money and complete watertightness.
TL-5™ is also available in cyclonic regions using long lasting ZINCALUME® and COLORBOND® steel, making it the perfect choice for both commercial or domestic use.
Material Specifications
Property | Notes | ||||
Base Metal Thickness (mm) | 0.35 | 0.42 | 0.48 | BMT | |
Total Coated Thickness (mm) | 0.40* | 0.47* | 0.53* | TCT | |
Mass / Unit Length | ZINCALUME® | 2.75 | 3.30 | 3.70 | kg/m |
COLORBOND® | 2.80* | 3.36* | 3.77* | ||
Mass / Unit Area | ZINCALUME® | 3.60 | 4.34 | 4.87 | kg/m2 |
COLORBOND® | 3.68* | 4.42* | 4.96* | ||
2nd moment of area about principal axis (103 mm4) | Ix | 32 | 39 | 45 | |
Iy | 19150 | 22980 | 26270 | ||
Section modulus about principal axis (103 mm3) | Zx | 2 | 2 | 2 | |
Zy | 47 | 56 | 64 | ||
Warping Constant (109 mm6) | Iw | 2 | 2 | 3 | |
Torsion Constant (mm4) | J | 14 | 23 | 35 | |
Minimum Yield Strength | G550 | Base Steel Designation | |||
Coating Class | Z600 (Heritage Galvanised) AM100 (COLORBOND® Steel) AM125 (ZINCALUME®) AM150 (COLORBOND® Ultra Steel) Z450 (Galvanised) | Minimum Coating g/m2 of Zinc - Aluminium |
|||
Coverage (mm) | 762 | ||||
Tolerance | Sheet Length ±7mm Cover Width ±4mm | ||||
Thermal Expansion | 2.9mm average per 5m at 50°C change |
Note:
- TL-5TM is manufactured from materials in accordance to AS 1397 and AS 2728. It is to be installed in accordance with AS 1562 and HB 39.
- The sectional properties are theoretical values per sheet width. These properties are gross values only.
- *is based on Standard COLORBOND®; single-sided material. For other painted steel options please contact a Fielders® representative.
Rainfall Capacity
For further information, please refer to sections "Rainfall Intensity" and "Water Carrying Capacity and Rainwater Run-Off".
TL-5™ Maximum Roof Length (m)
Roof Slope (degrees) | Rainfall Capacity (mm/hr) | ||||||
100 | 150 | 200 | 250 | 300 | 350 | 400 | |
2 | 172 | 114 | 86 | 69 | 57 | 49 | 43 |
3 | 210 | 140 | 105 | 84 | 70 | 60 | 53 |
4 | 243 | 162 | 121 | 97 | 81 | 69 | 61 |
5 | 272 | 181 | 136 | 109 | 91 | 78 | 68 |
Notes:
- Minimum recommended slope is 2°.
- Sheet lengths greater than 24m are not recommended due to thermal expansion and contraction.
Load Span Tables
Cyclonic Testing
Fielders® have undertaken cyclonic testing of TL-5TM in accordance with the Low-High- Low cyclonic testing method in the NCC (BCA).
The cyclonic wind load capacities for TL-5TM roofing profile are shown in Table TL WC CY 001 below.
Wind Load Capacity: Strength Limit State Design: 0.42mm BMT
Span (mm) | End (kPa) | Internal (kPa) |
900 | 6.50 | - |
1200 | 3.95 | 5.96 |
1500 | 2.66 | 3.99 |
1800 | 1.94 | 2.87 |
2100 | - | 2.17 |
Wind Load Capacity: Strength Limit State Design: 0.48mm BMT
Span (mm) | End (kPa) | Internal (kPa) |
900 | 7.21 | - |
1200 | 4.85 | 6.81 |
1500 | 3.29 | 4.86 |
1800 | 2.52 | 3.51 |
2100 | - | 2.76 |
Figure TL CY 001 End Spans, Internal Spans and Overhangs illustrates the terminology end spans, internal spans, and overhangs and their reference to the supporting substructure. This terminology has been used in the following Maximum Recommended Span and Wind Load Capacity tables.
Maximum Allowable Roof Spans* for building heights ≤ 5m: Region C
Terrain Category | Roof Area Notation & Uplift (kPa)* | 0.42 BMT | 0.48 BMT | ||
End (mm) | Internal (mm) | End (mm) | Internal (mm) | ||
1 & 2 | D - 4.18 | 1170 | 1460 | 1310 | 1630 |
F - 5.35 | 1020 | 1270 | 1130 | 1410 | |
G - 6.53 | 900 | 1150 | 980 | 1240 | |
2.5 | D - 3.54 | 1270 | 1600 | 1440 | 1790 |
F - 4.54 | 1120 | 1400 | 1250 | 1560 | |
G - 5.54 | 1000 | 1250 | 1100 | 1380 |
Pa,r = 1:500
Vr = 66 m/s for Region C
Vr = 88 m/s for Region D
Md = 1.00
Fc = 1.05
FD = 1.1
Ms = 1.00
Mt = 1.00
Cp,i = 0.70
Cp,e = - 0.90
KL = 1.5 for Area F
KL = 2.0 for Area G
Table TL RS CY 001A - TL-5™ Cyclonic
Notes:
- * Pressure is total ultimate value
Maximum Allowable Roof Spans* for building heights ≤ 5m: Region D
Terrain Category | Roof Area Notation & Uplift (kPa)* | 0.42 BMT | 0.48 BMT | ||
End (mm) | Internal (mm) | End (mm) | Internal (mm) | ||
1 & 2 | D - 6.66 | 880 | 970 | 1095 | 1225 |
F - 8.54 | 660 | 730 | 805 | 935 | |
G - 10.41 | 440 | 495 | 520 | 645 | |
2.5 | D - 5.65 | 1000 | 1100 | 1245 | 1280 |
F - 7.24 | 815 | 895 | 1005 | 1135 | |
G - 8.83 | 625 | 695 | 765 | 890 |
Pa,r = 1:500
Vr = 66 m/s for Region C
Vr = 88 m/s for Region D
Md = 1.00
Fc = 1.05
FD = 1.1
Ms = 1.00
Mt = 1.00
Cp,i = 0.70
Cp,e = - 0.90
KL = 1.5 for Area F
KL = 2.0 for Area G
Table TL RS CY 001B - TL-5™ Cyclonic
Notes:
- * Pressure is total ultimate value
Maximum Allowable Roof Spans* for building heights between 5m-10m: Region C
Terrain Category | Roof Area Notation & Uplift (kPa)* | 0.42 BMT | 0.48 BMT | ||
End (mm) | Internal (mm) | End (mm) | Internal (mm) | ||
1 & 2 | D - 4.18 | 1100 | 1380 | 1230 | 1540 |
F - 5.35 | 960 | 1200 | 1050 | 1320 | |
G - 6.53 | 830 | 1070 | 900 | 1140 | |
2.5 | D - 3.54 | 1170 | 1460 | 1320 | 1640 |
F - 4.54 | 1020 | 1280 | 1130 | 1420 | |
G - 5.54 | 900 | 1150 | 980 | 1250 |
Pa,r = 1:500
Vr = 66 m/s for Region C
Vr = 88 m/s for Region D
Md = 1.00
Fc = 1.05
FD = 1.1
Ms = 1.00
Mt = 1.00
Cp,i = 0.70
Cp,e = - 0.90
KL = 1.5 for Area F
KL = 2.0 for Area G
Table TL RS CY 002A - TL-5™ Cyclonic
Notes:
- * Pressure is total ultimate value
Maximum Allowable Roof Spans* for building heights between 5m-10m: Region D
Terrain Category | Roof Area Notation & Uplift (kPa)* | 0.42 BMT | 0.48 BMT | ||
End (mm) | Internal (mm) | End (mm) | Internal (mm) | ||
1 & 2 | D - 7.38 | 795 | 880 | 985 | 1110 |
F - 9.46 | 550 | 615 | 665 | 790 | |
G - 11.54 | 305 | 350 | 350 | 470 | |
2.5 | D - 6.59 | 890 | 890 | 1105 | 1235 |
F - 8.45 | 670 | 670 | 820 | 950 | |
G - 10.30 | 455 | 455 | 7540 | 665 |
Pa,r = 1:500
Vr = 66 m/s for Region C
Vr = 88 m/s for Region D
Md = 1.00
Fc = 1.05
FD = 1.1
Ms = 1.00
Mt = 1.00
Cp,i = 0.70
Cp,e = - 0.90
KL = 1.5 for Area F
KL = 2.0 for Area G
Table TL RS CY 002B - TL-5™ Cyclonic
Notes:
- * Pressure is total ultimate value
Allowable Roof Spans
The allowable roof spans for the TL-5TM roofing profile in Region C are shown in Table TL RS CY 001 and Table TL RS CY 002.
The allowable spans have been determined from tests carried out in accordance with AS4040.0-1992, AS 1170.2-2011 and the NCC (BCA) 2016 Specification B1.2 for the design of buildings in cyclonic areas.
Fixing of Cladding
Fasteners must be selected to match the life expectancy of the cladding material. Recommendations from fastener manufacturers should be sought. Only fasteners complying with AS 3566:2002 and those that are compatible with the roofing material should be used for its fastening.
All fasteners used externally should be fitted with an EPDM seal. Do not use punches to form fastener holes. Fasteners are to be fixed at each crest of the TL-5™ roof sheeting.
Insulation
Care needs to be taken when installing insulation with roof sheeting. When insulation thickness up to 50mm are installed the screws detailed in Table TL PF NC 001 may need to be increased depending on the thickness and density of the insulation. When the screw is properly tightened into metal there should be a minimum of three (3) threads protruding past the support being fixed in to. For timber the screw must penetrate the timber as much as the screws detailed in Table TL PF NC 001 do without insulation.
For insulation thicknesses greater than 50mm Fielders® recommend the use of a thermal spacer to help maintain Rw values as well as minimising any bulging in the profile caused by the insulation.
TL-5™ Installation Procedure
For installation procedures see section “Typical Pierce Fix Installation Guide”. For general handling instructions refer to section “Maintenance and Care”
Turning of Roof Sheeting Ends
Refer to section “Flashings, Cappings & Ends of sheets”.
Maximum Sheet Length
See section “Thermal Expansion and Contraction of Steel Sheeting”.
Curving
For details regarding spring fixing and crank curving of TL-5TM sheets, please see section “Curving of Steel Decks”.
TL-5™ Flashings & Details
Table TL FD CY 001
Notes:
1. * denotes size to be determined by application. All sizes are in mm and should be used as a guide only. They should be measured on-site to determine actual size.
2. S.B. denotes ‘Slight Break’.
3. Also refer to “Typical Roofing Details”.