TL-5™ Cyclonic

About TL-5™

TL-5™ is both versatile and economical, making it perfect for wall panelling, cladding or even short span roofing. The TL-5™ profile is quick and easy to install, long lasting and durable. With a rib height of 28mm, a large sheet coverage of 762mm, and specially design capillary grooves, TL-5™ offers excellent value for money and complete watertightness.

TL-5™ is also available in cyclonic regions using long lasting ZINCALUME® and COLORBOND® steel, making it the perfect choice for both commercial or domestic use.

TL-5™ CYCLONIC Profile

TL-5™ CYCLONIC Profile Cross Section

Material Specifications

PropertyNotes
Base Metal Thickness (mm)0.350.420.48BMT
Total Coated Thickness (mm)0.40*0.47*0.53*TCT
Mass / Unit LengthZINCALUME®2.753.303.70kg/m
COLORBOND®2.80*3.36*3.77*
Mass / Unit AreaZINCALUME®3.604.344.87kg/m2
COLORBOND®3.68*4.42*4.96*
2nd moment of area about principal axis (103 mm4)Ix323945
Iy191502298026270
Section modulus about principal axis (103 mm3)Zx222
Zy475664
Warping Constant (109 mm6)Iw223
Torsion Constant (mm4)J142335
Minimum Yield StrengthG550Base Steel Designation
Coating ClassZ600 (Heritage Galvanised)
AM100 (COLORBOND® Steel)
AM125 (ZINCALUME®)
AM150 (COLORBOND® Ultra Steel)
Z450 (Galvanised)
Minimum Coating g/m2 of Zinc -
Aluminium
Coverage (mm)762
ToleranceSheet Length ±7mm Cover Width ±4mm
Thermal Expansion2.9mm average per 5m at 50°C change
Table TL MS CY 001 - TL-5™ Cyclonic
Note:
  1. TL-5TM is manufactured from materials in accordance to AS 1397 and AS 2728. It is to be installed in accordance with AS 1562 and HB 39.
  2. The sectional properties are theoretical values per sheet width. These properties are gross values only.
  3. *is based on Standard COLORBOND®; single-sided material. For other painted steel options please contact a Fielders® representative.

Rainfall Capacity

For further information, please refer to sections "Rainfall Intensity" and "Water Carrying Capacity and Rainwater Run-Off".

TL-5™ CYCLONIC Rainfall Capacity Figure TL RC CY 001

Figure TL RC CY 001

TL-5™ Maximum Roof Length (m)

Roof Slope
(degrees)
Rainfall Capacity (mm/hr)
100150200250300350400
21721148669574943
321014010584706053
424316212197816961
5272181136109917868
Table TL RL CY 001 - TL-5™ Cyclonic
Notes:
  1. Minimum recommended slope is 2°.
  2. Sheet lengths greater than 24m are not recommended due to thermal expansion and contraction.

Load Span Tables

Cyclonic Testing

Fielders® have undertaken cyclonic testing of TL-5TM in accordance with the Low-High- Low cyclonic testing method in the NCC (BCA).

The cyclonic wind load capacities for TL-5TM roofing profile are shown in Table TL WC CY 001 below.

Wind Load Capacity: Strength Limit State Design: 0.42mm BMT

Span (mm)End (kPa)Internal (kPa)
9006.50-
12003.955.96
15002.663.99
18001.942.87
2100-2.17
Table TL WC CY 001A - TL-5™ Cyclonic

Wind Load Capacity: Strength Limit State Design: 0.48mm BMT

Span (mm)End (kPa)Internal (kPa)
9007.21-
12004.856.81
15003.294.86
18002.523.51
2100-2.76
Table TL WC CY 001B - TL-5™ Cyclonic

 

Figure TL CY 001 End Spans, Internal Spans and Overhangs illustrates the terminology end spans, internal spans, and overhangs and their reference to the supporting substructure. This terminology has been used in the following Maximum Recommended Span and Wind Load Capacity tables.

TL-5™ CYCLONIC Figure TL CY 001 End Spans, Internal Spans and Overhangs

Figure TL CY 001 End Spans, Internal Spans and Overhangs

Maximum Allowable Roof Spans* for building heights ≤ 5m: Region C

Terrain
Category
Roof Area
Notation &
Uplift (kPa)*
0.42 BMT0.48 BMT
End (mm)Internal (mm)End (mm)Internal (mm)
1 & 2D - 4.181170146013101630
F - 5.351020127011301410
G - 6.5390011509801240
2.5D - 3.541270160014401790
F - 4.541120140012501560
G - 5.541000125011001380
Wind Loading Design Parameters
+
Max. Roof Pitch <100
   
Pa,r = 1:500
   Vr = 66 m/s for Region C
   Vr = 88 m/s for Region D
   Md = 1.00
   Fc = 1.05
   FD = 1.1
   Ms = 1.00
   Mt = 1.00
   Cp,i = 0.70
   Cp,e = - 0.90
   KL = 1.5 for Area F
   KL = 2.0 for Area G

Table TL RS CY 001A - TL-5™ Cyclonic
Notes:
  1. * Pressure is total ultimate value

Maximum Allowable Roof Spans* for building heights ≤ 5m: Region D

Terrain
Category
Roof Area
Notation &
Uplift (kPa)*
0.42 BMT0.48 BMT
End (mm)Internal (mm)End (mm)Internal (mm)
1 & 2D - 6.6688097010951225
F - 8.54660730805935
G - 10.41440495520645
2.5D - 5.651000110012451280
F - 7.2481589510051135
G - 8.83625695765890
Wind Loading Design Parameters
+
Max. Roof Pitch <100
   
Pa,r = 1:500
   Vr = 66 m/s for Region C
   Vr = 88 m/s for Region D
   Md = 1.00
   Fc = 1.05
   FD = 1.1
   Ms = 1.00
   Mt = 1.00
   Cp,i = 0.70
   Cp,e = - 0.90
   KL = 1.5 for Area F
   KL = 2.0 for Area G

Table TL RS CY 001B - TL-5™ Cyclonic
Notes:
  1. * Pressure is total ultimate value

Maximum Allowable Roof Spans* for building heights between 5m-10m: Region C

Terrain
Category
Roof Area
Notation &
Uplift (kPa)*
0.42 BMT0.48 BMT
End (mm)Internal (mm)End (mm)Internal (mm)
1 & 2D - 4.181100138012301540
F - 5.35960120010501320
G - 6.5383010709001140
2.5D - 3.541170146013201640
F - 4.541020128011301420
G - 5.5490011509801250
Wind Loading Design Parameters
+
Max. Roof Pitch <100
   
Pa,r = 1:500
   Vr = 66 m/s for Region C
   Vr = 88 m/s for Region D
   Md = 1.00
   Fc = 1.05
   FD = 1.1
   Ms = 1.00
   Mt = 1.00
   Cp,i = 0.70
   Cp,e = - 0.90
   KL = 1.5 for Area F
   KL = 2.0 for Area G

Table TL RS CY 002A - TL-5™ Cyclonic
Notes:
  1. * Pressure is total ultimate value

Maximum Allowable Roof Spans* for building heights between 5m-10m: Region D

Terrain
Category
Roof Area
Notation &
Uplift (kPa)*
0.42 BMT0.48 BMT
End (mm)Internal (mm)End (mm)Internal (mm)
1 & 2D - 7.387958809851110
F - 9.46550615665790
G - 11.54305350350470
2.5D - 6.5989089011051235
F - 8.45670670820950
G - 10.304554557540665
Wind Loading Design Parameters
+
Max. Roof Pitch <100
   
Pa,r = 1:500
   Vr = 66 m/s for Region C
   Vr = 88 m/s for Region D
   Md = 1.00
   Fc = 1.05
   FD = 1.1
   Ms = 1.00
   Mt = 1.00
   Cp,i = 0.70
   Cp,e = - 0.90
   KL = 1.5 for Area F
   KL = 2.0 for Area G

Table TL RS CY 002B - TL-5™ Cyclonic
Notes:
  1. * Pressure is total ultimate value

Allowable Roof Spans

The allowable roof spans for the TL-5TM roofing profile in Region C are shown in Table TL RS CY 001 and Table TL RS CY 002.

The allowable spans have been determined from tests carried out in accordance with AS4040.0-1992, AS 1170.2-2011 and the NCC (BCA) 2016 Specification B1.2 for the design of buildings in cyclonic areas.

TL-5™ CYCLONIC Allowable Roof Spans Figure TL CY Local Pressure Factors 002

Figure TL CY Local Pressure Factors 002

Note:
The local pressure factors (KL) are shown in Figure TL CY Local Pressure Factors 002 are not applicable at the ridge where the roof pitch is less than 10°. The value of ‘a’ is the minimum of 0.2 breadth, 0.2 width or the height.

Fixing of Cladding

Fasteners must be selected to match the life expectancy of the cladding material. Recommendations from fastener manufacturers should be sought. Only fasteners complying with AS 3566:2002 and those that are compatible with the roofing material should be used for its fastening.

All fasteners used externally should be fitted with an EPDM seal. Do not use punches to form fastener holes. Fasteners are to be fixed at each crest of the TL-5™ roof sheeting.

Pierce Fixing

Fixing SupportsCrest FixingValley Fixing (Wall Only)Side Lap
Fixing
Steel
1.0 to 3.5mm
114-10x50mm
Metal Teks hex head
Square-Lok cyclone assembly
14-10x25mm
Metal Teks hexagon
head Ext Pt/Seal
10x16mm Hex Head Tek Screws with Neo washers
Table TL PF CY 001 - TL-5™ Cyclonic

Insulation

Care needs to be taken when installing insulation with roof sheeting. When insulation thickness up to 50mm are installed the screws detailed in Table TL PF NC 001 may need to be increased depending on the thickness and density of the insulation. When the screw is properly tightened into metal there should be a minimum of three (3) threads protruding past the support being fixed in to. For timber the screw must penetrate the timber as much as the screws detailed in Table TL PF NC 001 do without insulation.

For insulation thicknesses greater than 50mm Fielders® recommend the use of a thermal spacer to help maintain Rw values as well as minimising any bulging in the profile caused by the insulation.

TL-5™ Installation Procedure

For installation procedures see section Typical Pierce Fix Installation Guide”. For general handling instructions refer to section Maintenance and Care

Turning of Roof Sheeting Ends

Refer to section Flashings, Cappings & Ends of sheets”.

Maximum Sheet Length

Curving

For details regarding spring fixing and crank curving of TL-5TM sheets, please see section Curving of Steel Decks”.

TL-5™ Flashings & Details

Masonry Parapet Side Wall (Low)

TL-5™ CYCLONIC Flashings & Details Masonry Parapet Side Wall (Low) Product Code: TF1 

Product Code: TF1 

Masonry Parapet Side Wall (High)

TL-5™ CYCLONIC Flashings & Details Masonry Parapet Side Wall (High) Product Code: TF2 

Product Code: TF2 

Apron Flashings

TL-5™ CYCLONIC Flashings & Details Apron Flashings Product Code: TF3  GIRTH 330

Product Code: TF3 
GIRTH 330

Overflashing

TL-5™ CYCLONIC Flashings & Details Overflashing Product Code: TF4 GIRTH 112

Product Code: TF4
GIRTH 112

Headwall Apron Flashing

TL-5™ CYCLONIC Flashings & Details Headwall Apron Flashing Product Code: SF5 GIRTH 350

Product Code: SF5
GIRTH 350

Soaker Gutter

TL-5™ CYCLONIC Flashings & Details Soaker Gutter Product Code: TF6  GIRTH 350

Product Code: TF6 
GIRTH 350

Soffit Corner Flashing

TL-5™ CYCLONIC Flashings & Details Soffit Corner Flashing Product Code: TF7 GIRTH 211

Product Code: TF7
GIRTH 211

Shoe Flashing

TL-5™ CYCLONIC Flashings & Details Shoe Flashing Product Code: TF8

Product Code: TF8

Offset Wall Flashing
Type 1

TL-5™ CYCLONIC Flashings & Details Offset Wall Flashing Type 1 Product Code: SF9 GIRTH 150

Product Code: SF9
GIRTH 150

Offset Wall Flashing
Type 2

TL-5™ CYCLONIC Flashings & Details Offset Wall Flashing Type 2 Product Code: TF10

Product Code: TF10

Valley Gutter

TL-5™ CYCLONIC Flashings & Details Valley Gutter Product Code: TF11 GIRTH 340

Product Code: TF11
GIRTH 340

Under Over Flashing

TL-5™ CYCLONIC Flashings & Details Under Over Flashing Product Code: TF12 GIRTH 330

Product Code: TF12
GIRTH 330

Mansard Roof Flashing

TL-5™ CYCLONIC Flashings & Details Mansard Roof Flashing Product Code: TF13 GIRTH 330

Product Code: TF13
GIRTH 330

Industrial Door Jamb Flashing

TL-5™ CYCLONIC Flashings & Details Industrial Door Jamb Flashing Product Code: TF14 GIRTH 182

Product Code: TF14
GIRTH 182

Opening Jamb Flashing

TL-5™ CYCLONIC Flashings & Details Opening Jamb Flashing Product Code: TF15

Product Code: TF15

Door Head Flashing

TL-5™ CYCLONIC Flashings & Details Door Head Flashing Product Code: TF16 GIRTH 100

Product Code: TF16
GIRTH 100

Apex Capping
Type 1

TL-5™ CYCLONIC Flashings & Details Apex Capping Type 1 Product Code: TF17 GIRTH 290

Product Code: TF17
GIRTH 290

Apex Capping
Type 2

TL-5™ CYCLONIC Flashings & Details Apex Capping Type 2 Product Code: TF18 GIRTH 270

Product Code: TF18
GIRTH 270

Back Channel

TL-5™ CYCLONIC Flashings & Details Back Channel Product Code: TF19 GIRTH 110

Product Code: TF19
GIRTH 110

External Corner & Barge Capping

TL-5™ CYCLONIC Flashings & Details External Corner & Barge Capping Product Code: TF20 GIRTH 330

Product Code: TF20
GIRTH 330

Internal Corner Capping

TL-5™ CYCLONIC Flashings & Details Internal Corner Capping Product Code: TF21 GIRTH 330

Product Code: TF21
GIRTH 330

Barge Capping

TL-5™ CYCLONIC Flashings & Details Barge Capping Product Code: TF22 GIRTH 230

Product Code: TF22
GIRTH 230

Fragmented Parapet Capping

TL-5™ CYCLONIC Flashings & Details Fragmented Parapet Capping Product Code: TF23

Product Code: TF23

Two Piece Step Flashing

TL-5™ CYCLONIC Flashings & Details Two Piece Step Flashing Product Code: TF24

Product Code: TF24
Table TL FD CY 001

Notes:
1. * denotes size to be determined by application. All sizes are in mm and should be used as a guide only. They should be measured on-site to determine actual size.
2. S.B. denotes ‘Slight Break’.
3. Also refer to “Typical Roofing Details”.